MPC solution for optimal load shifting for buildings with ON/OFF staged packaged units: Experimental demonstration, and lessons learned
Journal Article
·
· Energy and Buildings
- Lawrence Berkeley National Lab. (LBNL), Berkeley, CA (United States)
- Purdue Univ., West Lafayette, IN (United States)
Small and medium-sized commercial buildings (SMCB) are significant demand response resources, and it is important to develop grid-responsive control algorithms that exploit those resources and create financial benefits for building owners and HVAC service providers. Furthermore, unlike large-sized commercial buildings, there is an opportunity to have universally applicable control solutions for many SMCBs since those buildings have a consistent HVAC system configuration: SMCBs are commonly served by multiple-staged air conditioning units controlled by their own thermostats. Despite the demand response potential and scalability, however, very few control solutions are available for SMCBs. Typical model predictive control (MPC) and heuristic control approaches for cooling load shifting that lower thermostat setpoints before an electric price jump are suitable mainly for large-sized commercial buildings where a continuous capacity modulation is possible, e.g., via dampers in variable air volume terminal units. However, those approaches can cause undesired, high peaks for SMCBs due to the nature of ON/OFF unit staging and narrow thermostat deadbands. This could discourage the use of advanced grid-responsive controls for SMCBs due to the concern of high demand charges, and has to be resolved. This paper presents a MPC solution that overcomes this challenge. It has a hierarchical MPC structure where an upper level MPC is responsible for electrical load shifting in response to an electric price signal while a lower level MPC is responsible for coordinating compressor stages to eliminate unnecessary peaks and follows the setpoints determined by the upper level MPC. In this work, two one-month, comprehensive laboratory tests have been carried out to demonstrate load shifting and cost savings for the algorithm. Interesting trade-offs between energy efficiency and load flexibility were observed and are discussed, and lessons learned for applying MPCs for SMCBs are also presented.
- Research Organization:
- Lawrence Berkeley National Laboratory (LBNL), Berkeley, CA (United States)
- Sponsoring Organization:
- USDOE Office of Energy Efficiency and Renewable Energy (EERE), Energy Efficiency Office. Building Technologies Office
- Grant/Contract Number:
- AC02-05CH11231
- OSTI ID:
- 1894470
- Journal Information:
- Energy and Buildings, Journal Name: Energy and Buildings Vol. 266; ISSN 0378-7788
- Publisher:
- ElsevierCopyright Statement
- Country of Publication:
- United States
- Language:
- English
Similar Records
Practical challenges of model predictive control (MPC) for grid interactive small and medium commercial buildings
Machine learning-enhanced MPC for demand flexibility in small commercial buildings: An experimental study
Evaluating Thermostats' Deadbands Using HVAC Hardware-In-the-Loop Experiment for Advanced Control Strategies
Conference
·
2024
·
OSTI ID:2439974
Machine learning-enhanced MPC for demand flexibility in small commercial buildings: An experimental study
Journal Article
·
2026
· Energy and Buildings
·
OSTI ID:3363413
Evaluating Thermostats' Deadbands Using HVAC Hardware-In-the-Loop Experiment for Advanced Control Strategies
Conference
·
2025
·
OSTI ID:2588191